InteliLite4 AMF20 Global Guide
332
Subgroup:COM2 Setting
COM2 Mode
Setpoint group CM-RS232-485 Related FW 1.3.0
Range [units] Direct / MODBUS / DualSlave / Dual Master [-]
Default value Direct Alternative config NO
Step [-]
Comm object 24451 Related applications AMF,MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Communication protocol switch for the COM2 channel.
Direct InteliConfig communication protocol via serial cable.
MODBUS MODBUS protocol.
DualSlave Dual operation protocol – slave function
DualMaster Dual operation protocol – master function
6 back to List of setpoints
COM2 Communication Speed
Setpoint group CM-RS232-485 Related FW 1.3.0
Range [units] 9600 / 19200 / 38400 / 57600 / 115200[bps]
Default value 57600 bps Alternative config NO
Step [-]
Comm object 24340 Related applications AMF,MRS
Config level Standard
Setpoint visibility
Only if relevant module is installed + conditioned by the setpoint COM2 Mode (page
332)
Description
If the direct mode is selected on COM2 channel, the direct communication speed of controller part of line
can be adjusted here. Speed of second part of line has to be adjusted to the same value.
6 back to List of setpoints