373
Nominal Frequency 1
Setpoint group Alternate Config Related FW 1.3.0
Range [units] 30 .. 65 [Hz]
Default value 50 Hz Alternative config YES
Step 1 Hz
Comm object 9913 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Nominal system frequency (usually 50 or 60 Hz).
Note: This value is used when any other alternate configuration is not active.
6 back to List of setpoints
Nominal Voltage Ph-N 1
Setpoint group Alternate Config Related FW 1.3.0
Range [units] 80 .. 20000 [V]
Default value 231 V Alternative config YES
Step 1 V
Comm object 12052 Related applications AMF,MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Connection type (page 209).
Description
Nominal system voltage (phase to neutral).
Note: This value is used when any other alternate configuration is not active.
6 back to List of setpoints
Nominal Voltage Ph-Ph 1
Setpoint group Alternate Config Related FW 1.3.0
Range [units] 80 .. 40000 [V]
Default value 400 V Alternative config YES
Step 1 V
Comm object 12055 Related applications AMF,MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Connection Type 1 (page 374).
Description
Nominal system voltage (phase to phase).
Note: This value is used when any other alternate configuration is not active.
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals