InteliLite4 AMF20 Global Guide
446
Related FW 1.3.0 Related applications AMF,MRS
Comm object 1060
Description
When this LBI is active, there is active alarm Wrn ECU Red Lamp (page 533) in alarmlist and ECU Red
Lamp icon in Aftertreatment HMI screen is shown.
ECU Red Lamp Solid
6 back to Logical binary inputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 164
Description
This binary input is used to set the setpoint ECU Speed Adjustment (page 255) by binary inputs. When
the LBI is activated the setpoint is decreased by 2%.
ECU Speed Down
6 back to Logical binary inputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 165
Description
This binary input is used to set the setpoint ECU Speed Adjustment (page 255) by binary inputs. When
the LBI is activated the setpoint is increase by 2%.
ECU Speed Up
6 back to Logical binary inputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 1064
Description
When this LBI is active, there is active alarm Wrn ECU Wait To Start (page 533) in alarmlist and ECU
Wait To Start Lamp icon in Aftertreatment HMI screen is blinking.
ECU Wait To Start Blink
6 back to Logical binary inputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 1065
Description
When this LBI is active, there is active alarm Wrn ECU Wait To Start (page 533) in alarmlist and ECU
Wait To Start Lamp icon in Aftertreatment HMI screen is blinking fast.
ECU Wait To Start Fast Blink
6 back to Logical binary inputs alphabetically