499
Related FW 1.3.0 Related applications AMF,MRS
Comm object 67
Description
The output is designed to be used as an indication that the Gen-set is running. The output is activated if
FUEL SOLENOID (PAGE 477) is active and STARTER (PAGE 501) and PRESTART (PAGE 496) are deactivated.
The out remains active until engine stop and cooling period elapses.
Image 8.56 Running
Running
6 back to Logical binary outputs alphabetically
LBO: S
Related FW 1.3.0 Related applications AMF,MRS
Comm object 962
Description
The output is active if SD OVERRIDE (PAGE 460) input is active and open if SD OVERRIDE (PAGE 460) input
is inactive. This output is usually used to send information about SD OVERRIDE (PAGE 460) input into ECU.
Sd Override
6 back to Logical binary outputs alphabetically