InteliLite4 AMF20 Global Guide
532
Alarm evaluated All the time
Related applications AMF,MRS
Description
The alarm indicates that there was a request to send an alarm SMS to telephone
number which is adjusted in setpoint Telephone Number 4 (page 351) and
SMS wasn't sent.
6 back to List of alarms level 1
Alarm Type WRN
Alarmlist message SNMP TRAP 1 Fail
Alarm evaluated All the time
Related applications AMF,MRS
Description This alarm is issued if TRAP will not be able to reach server.
Wrn SNMP TRAP 1 Fail
6 back to List of alarms level 1
Alarm Type WRN
Alarmlist message SNMP TRAP 2 Fail
Alarm evaluated All the time
Related applications AMF,MRS
Description
This alarm is issued if TRAP will not be able to reach server, or in case there is no
reply for the server
Wrn SNMP TRAP 2 Fail
6 back to List of alarms level 1
Alarm Type ALI
Alarmlist message ECUDiagBlocked
Alarm evaluated All the time
Related applications AMF,MRS
Description
LBO ALARM (PAGE 469) is not activated, after deactivation of lamp, alarm
automatically disappears.
Wrn ECUDiagBlocked
6 back to List of alarms level 1
Alarm Type WRN
Alarmlist message ECU Communication Fail
Alarm evaluated
With configured LBO ECU POWER RELAY (PAGE 474) – only when this LBO is
active
Without configured LBO ECU POWER RELAY (PAGE 474) – all the time
Related applications AMF,MRS
Description
This alarm occurs when an ECU is configured, but the communication with the
ECU is not established or has dropped out. LBO ALARM (PAGE 469) is not
activated, after deactivation of lamp, alarm automatically disappears.
Wrn ECU Communication Fail