InteliLite4 AMF20 Global Guide
559
Alarm Type SD
Alarmlist message EM(A) - missing or damaged
Alarm evaluated All the time
Related applications AMF,MRS
Description
This alarm indicates that there is a problem with communication with module in
slot (in first 5 second there was no communication and module is configured in
slot).
Sd EM(A) - missing or damaged
6 back to List of alarms level 2
Alarm Type SD
Alarmlist message EM(B) - missing or damaged
Alarm evaluated All the time
Related applications AMF,MRS
Description
This alarm indicates that there is a problem with communication with module in
slot (if first 5 second there was no communication and module is configured in
slot).
Sd EM(B) - missing or damaged
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd ECU Communication Fail
Alarm evaluated
With configured LBO ECU POWER RELAY (PAGE 474) – only when this LBO is
active
Without configured LBO ECU POWER RELAY (PAGE 474) – all the time
Related applications AMF,MRS
Description
This alarm occurs when an ECU is configured, but the communication with the
ECU is not established or has dropped out.
Sd ECU Communication Fail
6 back to List of alarms level 2
Alarm Type SD
Alarmlist message Emergency Stop
Alarm evaluated All the time
Related applications AMF,MRS
Description
Alarm is activated when binary input EMERGENCY STOP (PAGE 448) is activated.
The Gen-set shuts down in the moment the input is activated and starting is
blocked until the input is deactivated and fault reset is pressed.
Note: Use red emergency button placed on the switchboard door and
connect it to a binary input of the controller. Then configure the function
Emergency Stop to this binary input. It is recommended to use NC contact of
the button.
Sd Emergency Stop