InteliLite4 AMF20 Global Guide
560
Note: The MCB control is not affected by this alarm.
6 back to List of alarms level 2
Alarm Type SD
Alarmlist message Emergency Stop
Alarm evaluated All the time
Related applications AMF,MRS
Description
Alarm is activated when dedicated E-Stop input is activated. The Gen-set shuts
down in the moment the input is activated and starting is blocked until the input is
deactivated and fault reset is pressed.
Sd E-Stop
6 back to List of alarms level 2
Alarm Type SD
Alarmlist message Wrn Charging Alternator Fail
Alarm evaluated Engine running only
Related applications AMF,MRS
Description
This alarm is issued if the engine is running and the voltage on the D+ terminal is
lower than 80%D+ Threshold (page 243) of the controller supply voltage. This
alarm works similar to the red “battery” alarm indicator on a vehicle dashboard.
The setpoint has to be in Charge Fail or Enabled position to enable this alarm.
Sd Charging Alternator Fail
6 back to List of alarms level 2
Alarm Type SD
Alarmlist message Sd Overspeed
Alarm evaluated All the time
Related applications AMF,MRS
Description
This alarm occurs immediately when the engine speed has exceeded the limit.
The behavior of the overspeed alarm is adjusted by the following setpoints:
Overspeed Sd (page 244) adjust the overspeed limit
Sd Overspeed
6 back to List of alarms level 2
Alarm Type SD
Alarmlist message Sd Underspeed
Alarm evaluated Engine running only
Related applications AMF,MRS
Description
This alarm will be issued when the Gen-set is running and then stops by itself, i.e.
the RPM drops under the value of setpoint Underspeed Sd (page 246).
The underspeed alarm starts to be evaluated after successful Gen-set start and
is being evaluated for the entire time that the fuel solenoid is on.
Sd Underspeed