Sensors
NI1000 [°C] (fix) 0-10 kΩ 0-20 mA passive
PT100 [°F] (fix) ±1V ±20mA active
PT1000 [°F] (fix) 0-2.4V
CAN address
DIP switch determinates CAN address for analog inputs.
Note: When setting the CAN address to zero, the appropriate group of signals is deactivated.
Programming firmware
Firmware upgrade process:
1. Disconnect all terminals from the unit.
2. Remove the top cover of module
3. Put the TEST jumper on pins
4. Connect the unit with PC via RS232-null modem cable and AT-Link conv
5. Connect power supply of the module (status LED lights continuously)
6. Launch FlashPgr.exe PC software (version 4.2 or higher)
7. In FlashPrg program choose card Inteli AIN8 and load FW for the module
8. Set the proper COM port (connected with the unit) and press the Start button
9. Wait till process is done (If the process does not start – after 60 seconds the "Timeout" will be evaluated.
In this case please check: