3x CT (Current Transformer)
Autodetect
High Leg Delta
or
L1 >=100V; L1 <=160V
L2 >=160V
L3 >=100V; L3 <=160V
3PH3Wire or 3Ph4Wire
or
L1 >= 100V
L2 >= 100V
L3 >= 100V
3PH Low Y
or
L1 >=20V; L1 <=160V
L2 >=20V; L2 <=160V
L3 >=20V; L3 <=160V
L1L2 < 300V
L2L3 < 300V
L3L1 < 300V
3PH High Y
or
L1 > 160V
L2 > 160V
L3 > 160V
L1L2 >= 300V
L2L3 >= 300V
L3L1 >= 300V
SplPhL1L2
or
L1 >=100V
L2 >=100V
L3 <= 20V
SplPhL1L3
or
L1 >=100V
L2 <= 20V
L3 >=100V
Mono Phase
or
L1 >=100V
L2 <= 20V
L3 <= 20V
Voltage Autodetect shutdown
Note: To lock this setpoint against editing you also have to lock setpoint Connection Type 1 (page
353), Connection type 2 (page 357) and Connection type 3 (page 361).
6 back to List of setpoints