InteliLite Global Guide
29
Note: Recommended fusing is 3 A fuse.
IMPORTANT: 3 A fuse is calculated without BOUT consumption nor extension modules. Real value
of fuse depends on consumption of binary outputs and modules.
Example: Maximal consumption of binary outputs can be 22 A
2 x 10 A on high current outputs (for 10 seconds)
2 A on all others binary outputs
4.4.4 Measurement wiring
Use 1.5 mm
2
cables for voltage connection and 2.5 mm
2
for current transformers connection. Adjust
Connection type (page 193), Nominal Voltage Ph-N (page 195), Nominal Voltage Ph-Ph (page 195),
Nominal Current (page 191), PT Ratio (page 195), Vm PT Ratio (page 196) and CT Ratio (page 192) by
appropriate setpoints in the Basic Settings group.
IMPORTANT: Risk of personal injury due to electric shock when manipulating voltage terminals
under voltage. Be sure the terminals are not under voltage before touching them.
Do not open the secondary circuit of current transformers when the primary circuit is closed. Open
the primary circuit first.
CT Location
Image 4.2 CT Location
There are two options of CT location.
a) Load