InteliLite Global Guide
317
Setpoint group Scheduler Related FW 1.9.0
Range [units] 1 .. 5 [week]
Default value 1 week Alternative config NO
Step 1 week
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 2 Function (page 310)
Description
This setpoint adjust the week of month in which the Timer 2 Function (page 310) will be activated.
Timer 2 Repeat Week In Month
6 back to List of setpoints
Subgroup: Rental Timers
Setpoint group Scheduler Related FW 1.9.0
Range [units] Disabled / 1 .. 8 760 [h]
Default value Disabled Alternative config NO
Step 1 h
Comm object 14326 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Another engine start is not allowed when this timer elapsed. This timer is based on engine running hours. The
alarm Rental Timer 1 Elapsed (page 654) will be recorded in alarm list and the binary output AL RENTAL
TIMER 1 (PAGE 551) will close.
IMPORTANT: To reset Rental Timer 1 (page 317) we have to set up Rental Timer 1 (page 317)
again. It means go to setpoint group Scheduler and to the setpoint Rental Timer 1 (page 317).
Then press enter button , change the value if it is necessary and press enter button
again.
When the Rental Timer 1 (page 317) elapsed during engine run the gen-set will not stop immediately. The
adjustable Rental Timer BOC (page 321)timer will start in this moment. The engine will be cooled and
stopped when the Rental Timer BOC (page 321) time elapsed.
Rental Timer 1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals