InteliLite Global Guide
327
Setpoint group Plug-In Modules Related FW 1.9.0
Range [units] ENABLED / DISABLED [-]
Default value ENABLED Alternative config NO
Step [-]
Comm object 24279 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
This setpoint enable or disable module in slot B.
Slot B
6 back to List of setpoints
Group: CU AIN Calibration
Subgroup: Analog Input 1
Setpoint group CU AIN Calibration Related FW 1.9.0
Range [units] the range is defined by analog sensor curve
Default value
0 (number of decimal is
given by sensor curve)
Alternative config NO
Step the step is defined by analog sensor curve
Comm object 8431 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Calibrating constant to adjust the measured value of controller analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Note: Unit is adjusted via InteliConfig in configuration of analog input 1.
CU AIN1 Calibration
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals