InteliLite Global Guide
334
Setpoint group Scheduler Related FW 1.9.0
Range [units] 1 .. 5 [week]
Default value 1 week Alternative config NO
Step 1 week
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 1 Function (page 327)
Description
This setpoint adjust the week of month in which the Timer 1 Function (page 327) will be activated.
Timer 1 Repeat Week In Month
6 back to List of setpoints
Subgroup: Timer 2
Setpoint group Scheduler Related FW 1.9.0
Range [units] Disable / No Func / TEST / Test OnLd / MFail Blk / Mode OFF [-]
Default value No Func Alternative config NO
Step [-]
Comm object 15359 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
It is possible to choose from following Timer functions. Binary output EXERCISE TIMER 2 (PAGE 601) is
always activated when Timer is active regardless of chosen timer function. Timer functions require controller
running in AUTO mode.
Timer 1 has higher priority over Timer 2. So if Timer 1 Function (page 327) is configured for OFF mode and
Timer 2 Function (page 334) is over the same time configured for AUTO mode, controller will work in OFF
mode.
Controller activates timer whenever it is powered up even in period, where timer should be already running.
Disable The Timer is disabled.
No Func There is no any other function, only binary output of timer is activated.
TEST When this option is chosen then the binary output of timer is internally connected to the
binary input Remote TEST.
TEST OnLd When this option is chosen then the binary output of timer is internally connected to the
Remote TEST On Load binary input.
MFail Blk When this option is chosen then the binary output of timer is internally connected to the
Mains Fail Block binary input.
Mode OFF When this option is chosen then the binary output of timer is internally connected to the
Remote OFF binary input.
Timer 2 Function
6 back to List of setpoints