Subgroup: Analog Input 4
Setpoint group CU AIN Calibration Related FW 1.9.0
Range [units] the range is defined by analog sensor curve
Default value
0 (number of decimal is
given by sensor curve)
Alternative config NO
Step the step is defined by analog sensor curve
Comm object 8793 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Calibrating constant to adjust the measured value of controller analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Note: Unit is adjusted via InteliConfig in configuration of analog input 4.
CU AIN4 Calibration
6 back to List of setpoints
Group: Alternate Config
Subgroup: Basic settings
Setpoint group Basic settings Related FW 1.9.0
Range [units]
Mono Phase / SplPhL1L2 / SplPhL1L3 / 3Ph3Wire / 3Ph4Wire / High Leg D /
Autodetect [-]
Default value 3Ph4Wire Alternative config YES
Step [-]
Comm object 12058 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Connection type:
Mono Phase Single phase voltage measurement L1-N
1x CT (Current Transformer)
SplitPhase Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
2x CT (Current Transformer)
SplPhL1L2 Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
Connection Type 1