EasyManuals Logo

ComAp InteliLite AMF25 User Manual

ComAp InteliLite AMF25
735 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #330 background imageLoading...
Page #330 background image
InteliLite Global Guide
330
2x CT (Current Transformer)
SplPhL1L3 Double Delta connection
Split Phase
Two phase voltage measurement L1,L3 with 180° phase shift
2x CT (Current Transformer)
3Ph4Wire Grounded Star (Grounded Wye) connection 3PY
Three phase voltage measurement L1,L2,L3 with 120° phase shift
3x CT (Current Transformer)
3Ph3Wire Ungrounded Delta connection
Open Delta
Ungrounded Wye
Corner-Grounded Delta
Split Phase Delta
Three phase voltage measurement L1,L2,L3 with 120° phase shift
No neutral is available 3x CT (Current Transformer)
High Leg D High Leg Delta connection
Three phase voltage measurement L1,L2,L3
3x CT (Current Transformer)
Autodetect
High Leg Delta
or
L1 >=100V; L1 <=140V
L2 >=140V
L3 >=100V; L3 <=140V
3PH3Wire or 3Ph4Wire
or
L1 >=100V
L2 >=100V
L3 >=100V
SplPhL1L2
or
L1 >=100V
L2 >=100V
L3 <= 20V
SplPhL1L3
or
L1 >=100V
L2 <= 20V
L3 >=100V
Mono Phase
or
L1 >=100V
L2 <= 20V
L3 <= 20V
Voltage Autodetect shutdown
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 499) is active.
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals