InteliLite Global Guide
331
Setpoint group Basic settings Related FW 1.9.0
Range [units] 1 .. 10 000 [A]
Default value 350 A Alternative config YES
Step 1 A
Comm object 12049 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
It is current limit for generator current protections and means maximal continuous generator current. Nominal
Current can be different from generator rated current value.
Note: This value is used when any other alternate configuration is not active.
Nominal Current 1
6 back to List of setpoints
Setpoint group Basic settings Related FW 1.9.0
Range [units] 45 .. 65 [Hz]
Default value 50 Hz Alternative config YES
Step 1 Hz
Comm object 9913 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Nominal system frequency (usually 50 or 60 Hz).
Note: This value is used when any other alternate configuration is not active.
Nominal Frequency 1
6 back to List of setpoints
Setpoint group Basic settings Related FW 1.9.0
Range [units] 100 .. 4000 [RPM]
Default value 1 500 RPM Alternative config YES
Step 1 RPM
Comm object 9915 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Nominal engine speed (RPM - revolutions per minute).
Note: This value is used when any other alternate configuration is not active.
Nominal RPM 1
6 back to List of setpoints