InteliLite Global Guide
364
Setpoint group Basic settings Related FW 1.9.0
Range [units] 100 .. 4 000 [RPM]
Default value 1 500 RPM Alternative config YES
Step 1 RPM
Comm object 15196 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Nominal engine speed (RPM - revolutions per minute).
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 525) is active.
Nominal RPM 3
6 back to List of setpoints
Setpoint group Basic settings Related FW 1.9.0
Range [units] 80 .. 20 000 [V]
Default value 231 V Alternative config YES
Step 1 V
Comm object 12054 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Connection type 3 (page 361).
Description
Nominal system voltage (phase to neutral).
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 525) is active.
Nominal Voltage Ph-N 3
6 back to List of setpoints
Setpoint group Basic settings Related FW 1.9.0
Range [units] 80 .. 40 000 [V]
Default value 400 V Alternative config YES
Step 1 V
Comm object 12057 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Connection type 3 (page 361).
Description
Nominal system voltage (phase to phase).
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 525) is active.
Nominal Voltage Ph-Ph 3
6 back to List of setpoints