InteliLite Global Guide
724
Related applications AMF, MRS
Description
This alarm evaluates the generator phase to phase voltage between phases 1 and
2. The following setpoints are related to it:
Generator Undervoltage BOC (page 246)
Generator <> Voltage Delay (page 247)
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Generator L2 < Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase voltage in phases 2. The following
setpoints are related to it:
Generator Undervoltage BOC (page 246)
Generator <> Voltage Delay (page 247)
BOC Generator L2 < Voltage
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Generator L2L3 < Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase to phase voltage between phases 2 and
3. The following setpoints are related to it:
Generator Undervoltage BOC (page 246)
Generator <> Voltage Delay (page 247)
BOC Generator L2L3 < Voltage
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Generator L3 < Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase voltage in phases 3. The following
setpoints are related to it:
Generator Undervoltage BOC (page 246)
Generator <> Voltage Delay (page 247)
BOC Generator L3 < Voltage
6 back to List of alarms level 2