InteliLite Global Guide
725
Alarm Type BOC
Alarmlist message BOC Generator L3L1 < Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase to phase voltage between phases 3 and
1. The following setpoints are related to it:
Generator Undervoltage BOC (page 246)
Generator <> Voltage Delay (page 247)
BOC Generator L3L1 < Voltage
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Generator > Frequency
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Overfrequency BOC (page 248)
Generator <> Frequency Delay (page 249)
BOC Generator > Frequency
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Generator < Frequency
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Underfrequency BOC (page 249)
Generator <> Frequency Delay (page 249)
BOC Generator < Frequency
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Gen Voltage Unbalance ph-ph
Alarm evaluated Generator excited only
BOC Gen Voltage Unbalance Ph-Ph