Inputs and Outputs 
Hint: 
Any Binary input or output can be configured to any IL-NT controller terminal or changed to different 
function by LiteEdit software. There is fix 1 sec delay when any binary input is configured as 
protection. 
 
Binary inputs IL-NT  - default 
BI1   GCB Feedback 
BI2   MCB Feedback 
BI3   Emergency Stop  
BI4   Access Lock  
BI5   Remote OFF 
BI6   Remote TEST 
BI7  Sd Override  
Binary inputs – list 
Not Used 
Binary input has no function. Use this configuration when Binary input is not connected. 
Alarm  
If the input is closed (or opened) selected alarm is activated.   
Binary Alarm configuration items 
 
Name    14 characters ASCII string 
NC Normally closed Contact type 
NO Normally opened 
Warning  Alarm type 
Shut down   
All the time  Valid if checkbox “Engine running 
only” is not checked 
Alarm active 
Engine running only  Valid if checkbox “Engine running 
only” is checked 
GCB Feedback 
Use this input for indication, whether the generator circuit breaker is open or closed. 
If the feedback is not used, connect this input to the output GCB CLOSE/OPEN 
MCB Feedback 
This input indicates whether MCB is closed or opened. 
Emergency Stop 
If the input is opened, shut down is immediately activated. Input is inverted (normally closed) in default 
configuration.