– AMF20/25, SW version 1.2, ©ComAp – March 2008      64 
IL-NT-AMF-Reference Guide1.2.pdf 
AUT Mode 
 
The controller does not respond to buttons START, STOP, MCB ON/OFF, GCB ON/OFF. Engine 
start/stop request is evaluated form Mains failure/return.  
AMF sequence (simplified) 
State  Condition of the transition  Action  Next state 
Mains failed
1
 or MCB feedback dropout 
MCB Opens On = MAINSFAIL 
MCB CLOSE/OPEN off 
EmergStart Del timer 
started 
Mains failure 
Mains 
operation 
 
 
 
Mains failed
1
 or MCB feedback dropout 
MCB Opens On = GENRUN 
EmergStart Del timer 
started 
Mains failure 
Mains voltage and frequency OK 
MCB Opens On = MAINSFAIL 
After elapsing 
MCB Close 
Del 
MCB CLOSE/OPEN 
on 
 
Mains operation 
Mains voltage and frequency OK 
MCB Opens On = GENRUN 
 
None  Mains operation 
EmergStart Del elapsed 
MCB Opens On = MAINSFAIL 
Engine start sequence 
performed, then  
GCB CLOSE/OPEN on 
2
 
Island operation 
Mains 
failure 
EmergStart Del elapsed 
MCB Opens On = GENRUN 
 
Engine start sequence 
performed, then MCB 
CLOSE/OPEN off, time 
delay 
Fwd Return Del 
performed and GCB 
CLOSE/OPEN on 
2
 
 
Island operation 
Island 
operation 
Mains voltage and frequency OK  MainsReturnDel timer 
started 
Mains return 
Mains failed    Island operation Mains 
return 
MainsReturnDel elapsed  GCB CLOSE/OPEN off,  
then after 
Fwd Return Del 
MCB CLOSE/OPEN on 
and then engine stop 
sequence performed 
3
 
Mains operation 
 
1
 Mains failed means mains over/under -voltage, over/under -frequency, voltage assymetry (preset 
delay must elapse) 
 
2 
If during start-up sequence mains returns, then MCB is reclosed with delay MCB Close Del (if 
opened, depending on 
MCB Opens On setpoint) and start-up sequence is interrupted. 
 
3 
If mains fails during stop procedure (cooling) again, stop sequence is interrupted, MCB opened and 
GCB reclosedclosed with delay 
Fwd Return Del. 
 
 
See also chapter 
Circuit breakers timing. 
TEST mode  
 
The setpoint 
ReturnFromTEST influences the behavior of TEST mode. 
Caution: The gen-set starts automatically and is always running in TEST mode! 
The setpoint ReturnFromTEST = MANUAL 
While TEST mode is selected, gen-set starts and is running unloaded.