InteliLite
NT
– AMF20/25, SW version 1.2, ©ComAp – March 2008 63
IL-NT-AMF-Reference Guide1.2.pdf
State Condition of the transition Action Next state
RPM> Starting RPM
STARTER off
PRESTART off
Starting
D+ input activated or oil pressure detected
or Gen voltage > 25% Vgnom or D+ active
for 1s
STARTER off
PRESTART off
Cranking
MaxCrank Time elapsed, 1st attempt
STARTER off
FUEL SOLENOID off
STOP SOLENOID on
CrankFail Pause timer
started
Crank pause
Cranking
3
MaxCrank Time
elapsed, last attempt
STARTER off
PRESTART off
Shutdown (Start
fail)
Crank
pause
3
CrankFail Pause
elapsed
STARTER on
FUEL SOLENOID on
4
STOP SOLENOID off
MaxCrank Time counter
started
Cranking
80% Nominal RPM reached
READY TO LOAD on
1
Min, Max Stab Time
counter started
Running
RPM = 0 or any other shutdown condition FUEL SOLENOID off
STOP SOLENOID on
Shutdown
Starting
3
60 sec.
Elapsed
FUEL SOLENOID off
STOP SOLENOID on
Shutdown (Start
fail)
Stop request READY TO LOAD off
Cooling Time timer
started
Cooling
RPM = 0 or any other shutdown condition READY TO LOAD off
2
FUEL SOLENOID off
Shutdown
Running
GCB CLOSE/OPEN
closed
Loaded
GCB CLOSE/OPEN opened
Running
Loaded
RPM = 0 or any other shutdown condition FUEL SOLENOID off
STOP SOLENOID on
READY TO LOAD off
Shutdown
Cooling Time elapsed
FUEL SOLENOID off
STOP SOLENOID on
Stop
RPM = 0 or any other shutdown condition FUEL SOLENOID off
STOP SOLENOID on
Shutdown
Cooling
Start request READY TO LOAD on
1
Running
RPM = 0, Oil pressure not detected, Vgen <
10V, D+ not active
Ready
Stop
60 sec.
Elapsed
Stop (Stop fail)
1
if all generator parameters OK and Min Stab Time elapsed, indicates that GCB is possible to close.
In AUTO Mode closes in this moment GCB automatically.
2
If GCB output used GCB opens automatically
3
The start-up sequence can be interrupted in any time by comming stop request
4
Fuel solenoid is switched on with time advance of 1s fixed before starter motor is switched on.
Hint:
Threshold level for D+ input is 80% supply voltage, activation delay is 1s (to override short firings
during cranking – for example in cold conditions).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite NT AMF Series and is the answer not in the manual?

ComAp InteliLite NT AMF Series Specifications

General IconGeneral
BrandComAp
ModelInteliLite NT AMF Series
CategoryController
LanguageEnglish

Related product manuals