Setpoints 
Password 
EnterPassword 
Password is a four-digit number. Password enables change of relevant protected setpoints. 
Use 
↑ or  ↓  keys to set and ENTER key to enter the password.  
 
Hint: 
There is only 1 level of a password. 
ChangePassword  
Use  ↑ or  ↓  keys to set and ENTER  key to change the password. 
 
Hint
: 
At first the password has to be entered before the new password can be changed. 
Basic Settings 
Gen-set Name 
User defined name, used for InteliLite identification at remote phone or mobile connection. 
Gen-set Name is max 14 characters long and have to be entered using LiteEdit software. 
Nominal Power   [kW] 
Nominal power of the generator 
Step:     1kW 
Range:    1 –32000 kW 
Nomin Current      [ A ] 
It is current limit for generator *IDMT over current and short current protection and means maximal 
continuous generator current. See 
Gener Protect: *Amps IDMT Del, Short Crct Sd setpoints.  
Nominal Current can be different from generator rated current value. 
Step:   1 A 
Range:   1  -  10000 A 
CT Ratio    [/5A] 
Gen-set phases current transformers ratio. 
Step:     1 A 
Range:   1 – 5000 A / 5A 
 
Hint: 
For CT Ratio <= 250 the values of power and current are displayed in a controller with one decimal. 
For CT Ratio > 250 the values of power and current are displayed in a controller with integral 
numbers. If you change CT Ratio in LiteEdit or directly in the controller, decimal numbers will not be 
changed immediately. The change will be executed only by reconfiguring in LiteEdit. The statistics of 
power will be recounted at this time with regards to decimal numbers of power. 
WARNING! When you change the firmware, statistics can be invalid! 
PT Ratio    [/1] 
Gen-set potential transformers ratio. 
Step:     0,1  V / V 
Range:   0,1 – 500,0 V / V