Alarm Management
Following alarms are available:
Sensor fail
Warning
Shut down
Mains failure
Sensor fail (FLS)
Sensor fail is detected when measured value is 6% out of selected sensor characteristic, or data from
ECU is missing. Sensor fail is indicated by ##### symbol instead measured value.
Warning (WRN)
When warning comes up, only alarm outputs and common warning output are closed.
Possible warnings:
See List of possible events
Shut down (SD)
When the shut-down alarm comes up, InteliLite opens outputs GCB CLOSE/OPEN, FUEL
SOLENOID, STARTER and PRESTART to stop the engine immediately. Alarm outputs and common
shutdown output are closed. Active or not reset protection disables start.
Possible shut-down alarms:
See List of possible events
Mains failure (MF)
Mains failure detection depends on
Auto mains failure setpoints (levels and delays) adjusting. When
the mains failure comes up, mains circuit breaker is opened.
Possible mains failure reasons:
See List of possible events
Hint:
Mains failure is not written to alarm list!