EasyManuals Logo

ComAp InteliLite NT AMF Series User Manual

ComAp InteliLite NT AMF Series
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #67 background imageLoading...
Page #67 background image
InteliLite
NT
– AMF20/25, SW version 1.2, ©ComAp – March 2008 67
IL-NT-AMF-Reference Guide1.2.pdf
Alarm Management
Following alarms are available:
Sensor fail
Warning
Shut down
Mains failure
Sensor fail (FLS)
Sensor fail is detected when measured value is 6% out of selected sensor characteristic, or data from
ECU is missing. Sensor fail is indicated by ##### symbol instead measured value.
Warning (WRN)
When warning comes up, only alarm outputs and common warning output are closed.
Possible warnings:
See List of possible events
Shut down (SD)
When the shut-down alarm comes up, InteliLite opens outputs GCB CLOSE/OPEN, FUEL
SOLENOID, STARTER and PRESTART to stop the engine immediately. Alarm outputs and common
shutdown output are closed. Active or not reset protection disables start.
Possible shut-down alarms:
See List of possible events
Mains failure (MF)
Mains failure detection depends on
Auto mains failure setpoints (levels and delays) adjusting. When
the mains failure comes up, mains circuit breaker is opened.
Possible mains failure reasons:
See List of possible events
Hint:
Mains failure is not written to alarm list!

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite NT AMF Series and is the answer not in the manual?

ComAp InteliLite NT AMF Series Specifications

General IconGeneral
BrandComAp
ModelInteliLite NT AMF Series
CategoryController
LanguageEnglish

Related product manuals