InteliLite
NT
– AMF20/25, SW version 1.2, ©ComAp – March 2008 79
IL-NT-AMF-Reference Guide1.2.pdf
Remote Communication
Hint:
Refer to InteliCommunication guide for all additional information.
Internet connection
IL-NT controllers can be monitored from LiteEdit 3.0 over the Internet using Internet Bridge (IG-IB)
connected to the controller RS232 port.
Recommended ISDN modem
Askey TAS-200E
ASUScom TA-220ST
Develo Microlink ISDN i
Recommended GSM modem
Siemens M20, TC35, TC35i, ES75, MC39
Wavecom M1200/WMOD2
Wavecom - Maestro 20, dual 900/1800MHz.
Wavecom – Fastrack M1306B, dual 900/1800 MHz (Fastrack M1206B is NOT recommended)
FALCOM A2D, dual 900/1800MHz.
GSM Modem setup
Prior to start work with GSM modem run following program for GSM proper setup.
Program writes all the necessary AT commands to configure the GSM modem properly for use with IL-
NT.
This program runs independent on LiteEdit:
Start MS Windows-Start-Program files - LiteEdit –Gm_setup.exe.
Select COM port
Select iG-CU (=IS-CU) or iG-MU unit
Press Setup button
Follow commands in GSM Modem Setup window
Typical real baud rate for GSM data communication is 80 to 90 Bps.
Hint:
It is strongly recommended to use the same type of modem on the both sides (IL and PC) of
connection.
Analog
modem
Analog
modem
GSM
modem
GSM
modem
or
Mobile SIM card setting
Adjust SIM card in GSM modem following way:
enable data connection (when required)
no PIN code