InteliLite
NT
– AMF20/25, SW version 1.2, ©ComAp – March 2008      49 
IL-NT-AMF-Reference Guide1.2.pdf 
Step:       0.1 s 
Range:    0.0 – 600.0 s 
Gen  >V Sd       [%] 
Threshold for generator overvoltage. All three phases are checked. Maximum out of three is used. 
Step:       1% of  Nominal voltage 
Range:    0(Gen <V Sd) – 200%  
Gen  <V Sd       [%] 
Threshold for generator undervoltage. All three phases are checked. Minimum out of three is used. 
Step:    1% of Nominal voltage 
Range:    0% – 200 (Gen >V Sd)%  
Gen  V Del        [s] 
Delay for generator undervoltage and overvoltage alarm 
Step:       0.1s 
Range:     0.0 – 600.0 s 
Volt Unbal Sd      [%] 
Threshold for generator voltage unbalance alarm. 
Step:    1% of  Nominal voltage 
Range:   0 – 200% of  Nominal voltage 
Volt Unbal Del      [s] 
Delay for generator voltage unbalance alarm. 
Step:   0.1s 
Range:   0.0 – 600.0 s 
Gen  >Freq Sd      [%] 
Threshold for generator phase L3 overfrequency.  
Step:    0.1% of  Nominal frequency 
Range:   0 (Gen <Freq Sd) – 200.0% of Nominal frequency 
Gen  <Freq Sd      [%] 
Threshold for generator phase L3 underfrequency. 
Step:       0.1% of Nominal frequency 
Range:   0.0 – 200 (Gen >Freq Sd ) % of Nominal frequency 
Gen  Freq Del       [s] 
Delay for generator underfrequency and overfrequency alarm. 
Step:       0.1s 
Range:    0.0 – 600.0 s 
AutoMains Fail 
RetFromIsland      [ MANUAL, AUTO ] 
MANUAL:  After closing GCB, IL goes to MAN Mode automatically. 
AUTO:    No automatic switching to MAN Mode. 
EmergStart Del   [s] 
Delay after the mains failure to the start of the gen-set  
Step:   1s 
Range:   0 – 600 s 
MainsReturnDel    [s] 
Delay after the mains return to the GCB opening.