InteliLite
NT
– AMF20/25, SW version 1.2, ©ComAp – March 2008      73 
IL-NT-AMF-Reference Guide1.2.pdf 
Remote Control and Data Logging 
Direct connection to the PC 
 
InteliLite can be connected directly with PC via optional IL-NT RS232 interface.  
Use the standard serial cable to connect PC with InteliLite. 
 
Hint: 
Make sure the grounding system on controller and PC – COM port (negative of the PC DC supply) are 
identical – before the first direct connection. There must not be any voltage between these two points 
otherwise the internal reversible fuse in controller burns out. The simple solution is to assure, that the 
PC supply 240/20V is ground free (GND terminal is not connected). 
 
5 - GND
2 - RxD
3 - TxD
PC
5 - GND
2 - RxD
3 - TxD
RS232
RS232
230 VAC
0 VDC
CONTROLLER
+
-
Battery
Required the same
voltage  potential
between GND‘s
RS 232
 
PC software – LiteEdit 
 
On the PC (for direct or modem connection) has to be installed the ComAp’s software package 
LiteEdit. (based on Windows 95 or newer platform) 
LiteEdit enables: 
•  read the quantities 
•  adjust all set points 
•  control  the engine  
• configure the controller 
•  select software configuration 
•  modify alarm inputs and outputs 
•  modify password, commands protections 
•  direct, modem or Internet  communication 
Modbus protocol 
 
The selection of the function of iL serial port  is done via the setpoint 
RS232 mode in Basic settings 
 
•
  9600 bps, 8 data bits, 1 stop bit, no parity 
•  Transfer mode RTU 
•  Function 3 (Read Multiply Registers) 
•  Function 6 (Write Single Register) 
•  Function 16 (Write Multiply Registers) 
•  The response to an incoming message is sent with minimum 4.096 ms delay after message 
reception 
 
The complete description of Modbus communication protocol can be found in 
Modbus Protocol 
Reference Guide PI-MBUS-300
 and Open Modbus Specification Release 1.0. Both documents are 
available from web site at http://www.modicon.com/openmbus/
 .