Engine Params 
Starting RPM   [%] 
“Firing” speed when IL controller  stops cranking (starter goes OFF).  
Step:     1% of nominal RPM 
Range:    5 – 50  % 
Starting Oil P      [Bar] 
When reached controller stops cranking (starter goes OFF). 
Step:     0,1 bar 
Range:   0,0 – 10,0  
 
Hint
: 
There are three conditions for stop cranking: Starting RPM, Starting Oil P and D+ (when enabled). 
Starter goes off when any of these conditions is vaid. 
Prestart Time   [s] 
Time of closing of the Prestart output prior to the engine start. 
Set to zero if you want to leave the output 
Prestart open.  
Step:     1s 
Range:    0 – 600 s 
MaxCrank Time   [s] 
Maximum time limit of cranking.  
Step:     1s 
Range:    1 – 60 s 
CrnkFail Pause   [s] 
Pause between Crank Attempts.  
Step:     1s 
Range:    5 – 60 s 
Crank Attempts   [-] 
Max number of Crank Attempts.  
Step:     1 
Range:    1 – 10 
Idle Time     [s] 
Idle time delay starts when RPM exceeds Starting RPM. Start fail is detected  when during Idle state 
RPM decreases below 2.  
During the 
Idle time timer running the binary output Idle/Nominal is opened when it elapses the  
Idle/Nominal output closes.  Binary output Idle/Nominal opens during Cooling period again. 
Step:     1 s 
Range:    0 – 600 s