InteliLite
NT
– AMF20/25, SW version 1.2, ©ComAp – March 2008      72 
IL-NT-AMF-Reference Guide1.2.pdf 
History file 
 
InteliLite NT stores a record of each important event into the history file. The history file seats 117 
records. When the history file is full, the oldest records are removed. 
 
Hint
: 
To force history download in LiteEdit (direct,,modem or Internet) open History window and select 
History | Read history command. 
Record structure 
Abbreviation  Historical value  
Num  Number of historical event 
Reason Event specification 
Date  Date of historical event in format DD/MM/YY 
Time  Time of historical event in format HH:MM:SS 
RPM Engine speed 
Pwr  Generator active power 
PF Generator PF 
LChr  Character of the load 
Gfrq Generator frequency 
Vg1  Generator voltage L1 
Vg2  Generator voltage L2 
Vg3  Generator voltage L3 
Ig1  Generator current L1 
Ig2  Generator current L2 
Ig3  Generator current L3 
Mfrq Mains frequency 
Vg1  Mains voltage L1 
Vg2  Mains voltage L2 
Vg3  Mains voltage L3 
V Battery  Battery voltage 
OilP  IL-NT Analog input 1 value ( default Oil pressure) 
EngT  IL-NT Analog input 2 value ( default Water temperature) 
FLvl  IL-NT Analog input 3 value ( default Fuel level) 
AIM1  IG-IOM, IGS-PTM Analog input 1 value (when configured IG-IOM, IGS-PTM) 
AIM2  IG-IOM, IGS-PTM Analog input 2 value (when configured IG-IOM, IGS-PTM) 
AIM3  IG-IOM, IGS-PTM Analog input 3 value (when configured IG-IOM, IGS-PTM) 
AIM4  IG-IOM, IGS-PTM Analog input 4 value (when configured IG-IOM, IGS-PTM) 
BINARY 
INPUTS 
Binary inputs IL-NT 
BIM  IG-IOM, IGS-PTM Binary inputs (when configured IG-IOM, IGS-PTM) 
BINARY 
OUTPUTS 
Binary outputs IL-NT 
BOM  IG-IOM, IGS-PTM Binary outputs (when configured IG-IOM, IGS-PTM) 
FC  ECU alarm FailureCode 
FMI  ECUalarm Failure Mode Identifier