InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
107
AI: LdCtrl:I/E-Pm
Controller CTs
Process control:
I/E-Pm meas
Process control:
Import load
Pgen from CAN
+
-
7.9.3 IMP/EXP
Following diagram shows the way
of calculation of requested gen-set
group active power if
ProcessControl:Mload ctrl PtM =
IMP/EXP.
AI: LdCtrl:I/E-Pm
Controller CTs
Process control:
I/E-Pm meas
Process control:
Import load
+
-
AI: MLC:AnExI/E
7.9.4 ANEXT IMP/EXP
Following diagram shows the way
of calculation of requested gen-set
group active power if
ProcessControl:Mload ctrl PtM =
ANEXT IMP/EXP.
AI: LdCtrl:TByPwr
Process control:
TempByPwr Treq
-
PID LOOP
Process control:
TempByPwr gain
TempByPwr int
AI: LdCtrl:I/E-Pm
Controller CTs
Process control:
I/E-Pm meas
Process control:
Import load
Process control:
Export limit
ENABLED
DISABLED
Pgen from CAN
+
-
Pin
Pout
Required temperature of the system
Actual temperature
Baseload is increasing
Baseload is decrasing
Temperature of the system
Time
7.9.5 T BY PWR
Following diagram shows the way
of calculation of requested gen-set
group active power if
ProcessControl:Mload ctrl PtM = T
BY PWR.