possible
Description
This setpoint adjusts the reset (initial) value of the ExtValue 2. This initial
value is applied either when the controller is powered-on or when the
ExtValue 2 is reset by the binary input ExtValue2reset.
11.2.12.31 Setpoint: ExtValue3deflt
Group
Force value
Range [units]
-32000 .. 32000 [x]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint adjusts the reset (initial) value of the ExtValue 3. This initial
value is applied either when the controller is powered-on or when the
ExtValue 3 is reset by the binary input ExtValue3reset.
11.2.12.32 Setpoint: ExtValue4deflt
Group
Force value
Range [units]
-32000 .. 32000 [x]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint adjusts the reset (initial) value of the ExtValue 4. This initial
value is applied either when the controller is powered-on or when the
ExtValue 4 is reset by the binary input ExtValue4reset.
11.2.13 Group: Load shedding
11.2.13.1 Setpoint: Ld shed active
Group
Load shedding
Range [units]
DISABLED, ISLAND ONLY, ISL+TRIP PARAL, ALL THE TIME [-]
Related FW
standard v3.1.0
Force value
YES