The setpoint is used for adjustment when the load shedding function will be
active.
The Load shedding function is disabled. All the
outputs are open.
In Island operation (i.e. MCB is open and MGCB is
closed) Load shedding outputs (e.g. LdShed stage
1) are controlled by load shedding function.
This setting adjusts the same behavior as ISLAND
ONLY but in addition to it all load shedding outputs
are closed when gen-set group goes to island
operation. For more information see the chapter
Load shedding.
Outputs are controlled by the load shedding
function regardless of breaker positions.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.2 Setpoint: LdShedBased on
MAINS IMPORT, GENSETS [-]
This setpoint is used to select the control quantity for the load shedding
function.
The control quantity is active power imported from
the mains taken relative to the nominal mains import:
100 * MainsImport/NominMainsImp.
The control quantity is sum of the actual power of all
running gen-sets taken relative to he sum of their