, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
308
Related FW
standard v3.1.0
Description
The angle between the phasors of the bus and mains voltage.
12.1.2.13 Value: Bus V [kV]
Group
Bus values
Units
kV
Related FW
standard v3.1.0
Description
This value shows measured bus voltage in kV.
12.1.3 Group: Object values
12.1.3.1 Value: Object P
Group
Object
Units
kW
Related FW
standard v3.1.0
Description
This is actual active power consumption of the load. This value together with
value Object Q is used for calculation of Object PF.
12.1.3.2 Value: Object Q
Group
Object
Units
kVAr
Related FW
standard v3.1.0
Description
This is actual reactive power consumption of the load. This value together
with value Object P is used for calculation of Object PF.
12.1.3.3 Value: Object PF
Group
Object
Units
-