12.1.2.8 Value: Bus V L3-L1
Group
Bus values
Units
V
Related FW
standard v3.1.0
Description
Bus voltage phase L3 to L1.
12.1.2.9 Value: Bus V unbal
Group
Bus values
Units
V
Related FW
standard v3.1.0
Description
Bus voltage unbalance. The value is calculated as maximal difference of two
phase voltages at one moment and expressed in % of the bus nominal
voltage.
12.1.2.10 Value: I Aux
Group
Bus values
Units
A
Related FW
standard v3.1.0
Description
This value shows actual current measured at auxiliar terminals.
12.1.2.11 Value: Slip freq
Group
Bus values
Units
Hz
Related FW
standard v3.1.0
Description
Differential frequency between the bus and the mains.
12.1.2.12 Value: Angle