InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
Shared (virtual) Analog Input module
Shared (virtual) Analog OUTput
module
Programmable (internal) logic module.
NOTE:
Maximum number of configured modules (both extension and virtual) is given by available addresses.
The numbers in the table are valid in the case that no other modules are configured.
15.2 Table of analog input functions
15.2.1.1 Analog input: MLC:AnExSysBld
This input is used for external determination of system load.
15.2.1.2 Analog input: MLC:AnExI/E
This functional input is used for requesting the mains import value externally
by an analog input. The setpoint Load ctrl PtM must be set to ANEXT IM/EX
position.
15.2.1.3 Analog input: MLC:TByPwr
This functional input is used as the temperature input into the load control
loop if the loop is switched into "T BY PWR" position. More information is
available at the setpoint Load ctrl PtM.
15.2.1.4 Analog input: MPF:AnExI/E
This functional input is used for requesting the mains cos phi factor
externally by an analog input. The setpoint PF ctrl PtM must be set to ANEXT
PF-IM/EX position.
The analog value is transformed to the requested cos phi factor following
way: