11.2.11 Group: Volt/PF ctrl
11.2.11.1 Setpoint: Voltage gain
This setpoint adjusts the gain factor (P-factor) of the voltage control PI loop.
The integration factor (I-factor) for the voltage control loop is adjusted by the
setpoint Voltage int.
NOTE:
If this setpoint is set to 0 the regulation loop is disabled.
VOLTAGE GAIN AND VOLTAGE INT SETPOINTS ARE ACTIVE DURING:
reverse synchronization of the gen-set group back to the
mains
forward or reverse synchronization of the gen-set group to the
mains
synchronization between “left” and “right” buses
NOTE:
When this setpoint is set to zero, the corresponding control loop is switched
OFF.
NOTE:
See the chapter Regulation loops overview for general information about
regulation loops and their adjustment.