Pn is the nominal power of the gen-set which is next to be stopped, the upper
sum is the sum of the rest of the gen-sets running in power management.
The lower sum is the sum of all the gen-sets currently running in power
management.
#%LdResStop is used from the currently selected reserve set.
12.1.8 Group: Sync/Load ctrl
12.1.8.1 Value: ActPwrReq
Group
Sync/Load ctrl
Units
kW
Related FW
standard v3.1.0
Description
This value contains actual required load level, which is used as the input into
the load regulation loop in the parallel to mains operation.
12.1.8.2 Value: SystLoadCtrl
Group
Sync/Load ctrl
Units
-
Related FW
standard v3.1.0
Description
Code of the current load control mode. The text representation of each code
can be obtained by the procedure described at the value Timer text.
12.1.9 Group: Volt/PF ctrl
12.1.9.1 Value: SystPfCtrl
Group
Volt/PF ctrl
Units
-
Related FW
standard v3.1.0