12.1.7.7 Value: Reserve Stp
Actual absolute reserve - when the reserve is higher than this value the last
started gen-set (the gen-set with the highest priority) is stopped. This value
contains the following: #LoadResStop plus Nominal power of the genset
which is first to stop. #LoadResStop is used from the currently selected
reserve set.
12.1.7.8 Value: ActRes rel
12.1.7.9 Value: ResStart rel
If the actual relative reserve is lower than this value the next gen-set which is
about to be started in power managament is started. This value is the exact
copy of setpoint #%LdResStrt X.
12.1.7.10 Value: ResStp rel
Actual relative reserve - when the relative reserve is higher than this value
the last started gen-set (the gen-set with the highest priority) is stopped. This
value contains the following: