10 Controller operation states
These states are given by requested breaker positions and other parameters (e.g. healthy Mains).
Controller can operate in following states.
MainsOper
MCB application: MCB feedback is active, all GCB feedbacks are not active, Mains parameters
are within limits
MGCB application: MCB feedback is active, MGCB feedback is not active, Mains parameters
are within limits
MainsFlt
MCB application: Mains parameters are not within limits
MGCB application: MGCB feedback is not active, Mains parameters are not within limits
ValidFlt
MCB application: Mains parameters are not within limits and AMF settings:EmergStart del
elapsed
MGCB application: MGCB feedback is not active, Mains parameters are not within limits and
AMF settings:EmergStart del elapsed
IslOper
MCB application: MCB feedback is not active, at least one GCB feedback is active, Mains
parameters are not within limits
MGCB application: MCB feedback is not active, MGCB feedback is active, Mains parameters
are not within limits
MainsRet
MCB application: MCB feedback is not active, at least one GCB feedback is active, Mains
parameters are within limits
MGCB application: MCB feedback is not active, MGCB feedback is active, Mains parameters
are within limits
BrksOff
MCB application: MCB and all GCB feedback are not active
MGCB application: MCB and MGCB feedbacks are not active
Synchro
MGCB application: MCB feedback is active, MGCB feedback is not active, synchronization is
allowed and started
RevSync
MCB application: MCB feedback is not active, at least one GCB feedback is active, reverse
synchronization is allowed and started
MGCB application: MCB feedback is not active, MGCB feedback is active, reverse
synchronization is allowed and started
ParalOper
MCB application: MCB feedback is active, at least one GCB feedback is active
MGCB application: MCB and MGCB feedbacks are active
EmergMan
Controller is in this state if BI EMERG. MANUAL is activated. In this state controller does not react
on breaker changes and do not activate any of its binary outputs. For more information please
refer to EMERG. MANUAL description in the APPENDIX of this manual or see context help in
GenConfig.
Init
Initialization of controller. In this state, controller is not fully functional.