EasyManua.ls Logo

ComAp InteliMains NT IM-NT-BB - PI Regulation Adjustment

ComAp InteliMains NT IM-NT-BB
437 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
116
APPLICATION
VOLTAGE GAIN AND VOLTAGE INT SETPOINTS ARE ACTIVE DURING:
MCB
reverse synchronization of the gen-set group back to the mains
MGCB
forward or reverse synchronization of the gen-set group to the
mains
See also setpoints: Volt/PF ctrl:Voltage gain and Volt/PF ctrl:Voltage Int
When the Voltage gain is set to zero, this control loop is switched OFF.
COS-PHI LOOP
This regulation loop is active if setpoint ProcessControl:SysPFCtrl PtM is set to
VSHARING.
ProcessControl:SysLdCtrl PtM should be swithed to LDSHARING.
The IM power factor control mode is selected by the
setpoint ProcessControl:PF ctrl PtM.
ProcessControl:MLoad ctrl PtM should be set to the same value
as ProcessControl:PF ctrl PtM. Due to this Cos-phi regulation loop can be
active only in the Import/Export mode.
7.12.1 PI regulation adjustment
The regulation loops have two adjustable factors: P-factor and I-factor (except angle regulation loop,
which has P-factor only). The P-factor (gain) influences the stability and overshoot of the regulation
loop and the I-factor influences the steady-state error as well as the settling time. See the picture
below for typical responses of a PI regulation loop.
Figure: Typical responses of a PI regulator
For manual tunning of a control loop use following method:
1. Set both the I-factor and P-factor to 0.
2. Increase the P-factor slightly until the system starts to oscillate.
3. Adjust the P-factor back to approx. one half of the value where the oscillations started.
4. Increase the I-factor slightly to achieve optimal resulting response.
NOTE:
It may be helpful to disable issuing the breaker close command when adjusting synchronization loops.
Adjust the setpoint Phase window to 0 to disable it. Adjust the setpoint back to its original value after
the adjustment is finished.
CAUTION!

Table of Contents