EasyManua.ls Logo

ComAp InteliMains NT IM-NT-BB - Default Protections in MCB;MGCB Applications

ComAp InteliMains NT IM-NT-BB
437 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
136
1
History record
Hst
none
History only
NO
1
Alarm only
Al
none
Alarmlist only
YES
1
Warning
Wrn
none
Alarmlist and
History
YES
1
AL indication
ALI
none
Alarmlist only
NO
1
A+H indication
AHI
none
Alarmlist and
History
NO
2
Mains protection
MP
Controller opens MCB, no
fault reset needed after alarm
inactivation
When the breaker opens is
given by the setpoint
AMF settings:MCB open on
History only
NO
2
Mains protection
with fault reset
MPR
Controller opens MCB, MCB
cannot be closed before
alarm inactivation and fault
reset
When the breaker opens is
given by the setpoint
AMF settings:MCB open on
Alarmlist and
History
YES
X
Fail sensor
Fls
Can be indicated when
Analog input value is ±6%
out of sensor characteristic
range. Fls can optionally
activate corresponding (e.g.
Sd) Analog input protection
as well.
Alarmlist and
History
Configurable
8.1.3 Default protections in MCB/MGCB applications
Following protections are firmware based
PROTECTION
PROTECTION
TYPE
CORRESPONDING SETPOINTS
Mains:
IDMT Current
MPR
Mains protect: Mns2Inom prot;Mains2Inom del
IDMT Active Power
MPR
Mains protect: Mns2POvrldProt; OverlStrtEval;
2POvrldStEvDel
Vector Shift
MP
Mains protect: VectorS prot; VectorS limit; Vector
CB sel
ROCOF
MP
Mains protect: ROCOF prot; ROCOF Win,
ROCOF df/dt
Mains Voltage over and under
voltage in all phases
MP
Mains protect: Mains >V MP; Mains <V MP;
Mains V del
Mains Frequency over and
under frequency
MP
Mains protect: Mains >f; Mains <f; Mains f del
Average Mains Overvoltage
MP
Mains protect: Mains Avg>V MP