Controller opens MCB, no
fault reset needed after alarm
inactivation
When the breaker opens is
given by the setpoint
AMF settings:MCB open on
Mains protection
with fault reset
Controller opens MCB, MCB
cannot be closed before
alarm inactivation and fault
reset
When the breaker opens is
given by the setpoint
AMF settings:MCB open on
Can be indicated when
Analog input value is ±6%
out of sensor characteristic
range. Fls can optionally
activate corresponding (e.g.
Sd) Analog input protection
as well.
8.1.3 Default protections in MCB/MGCB applications
Following protections are firmware based
Mains protect: Mns2Inom prot;Mains2Inom del
Mains protect: Mns2POvrldProt; OverlStrtEval;
2POvrldStEvDel
Mains protect: VectorS prot; VectorS limit; Vector
CB sel
Mains protect: ROCOF prot; ROCOF Win,
ROCOF df/dt
Mains Voltage – over and under
voltage in all phases
Mains protect: Mains >V MP; Mains <V MP;
Mains V del
Mains Frequency – over and
under frequency
Mains protect: Mains >f; Mains <f; Mains f del
Average Mains Overvoltage
Mains protect: Mains Avg>V MP