EasyManua.ls Logo

ComAp InteliMains NT IM-NT-BB - Group: Basic Settings

ComAp InteliMains NT IM-NT-BB
437 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
175
11.2.1.32 Setpoint: MultiSoftStart
Group
ProcessControl
Range [units]
DISABLED, ENABLED [-]
Related FW
standard v3.1.0
Description
This setpoint enables StartUpSynchronization of a group of gen-sets with
closed MGCB prior to getting healthy voltage measurement on the bus.
DISABLED
There is no change in the controller behavior.
ENABLED
The controller will close MGCB in AUT and MAN right
after at least one of gen-set controllers in its control group
closes GCB and indicates StartUpSynchro sequence.
MGCB is not closed if MCB is closed (e.g. due to healthy
Mains)
11.2.1.33 Setpoint: Watched Contr
Group
Process Control
Range [units]
0 .. 16 [min]
Related FW
standard v3.1.0
Description
This setpoint is used at redundant controller to specify the address of the
related main controller in CAN-based rendundant systems. Adjust this
setpoint to 0 if the controller is not used as redundant or if wired rendundancy
system is used.
NOTE:
Learn more about redundant systems in the chapter Redundant controllers.
11.2.2 Group: Basic settings
11.2.2.1 Setpoint: Vm VT ratio
Group
Basic Settings
Range [units]
0.10 .. 500.00 [V/V]

Table of Contents