InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
281
Description
This setpoint is used to adjust time period for the load shedding stage 3, that
the control quantity must be below the Ld reconLevel3 limit to allow
reconnection of next load group.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.23 Setpoint: AutoLd recon
Group
Engine Protect
Range [units]
DISABLED, ENABLED [-]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint selects whether the reconnection of the load occurs
automatically when the control quantity stays below the reconnection limit for
a period of the reconnection delay or the reconnection must be initiated
manually by the input ManualLdRecon.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.14 Group: Timer settings
11.2.14.1 Setpoint: Timer channel 1
Group
Timer settings
Range [units]
[-]
Related FW
standard v3.1.0
Description
This setpoint adjusts the mode of the Timer channel #1. Output from this
channel is available in the combined output TimerAct 1-4.
NOTE:
See the chapter Timers for more details about timers.
11.2.14.2 Setpoint: Timer channel 2
Group
Timer settings