This setpoint is used to adjust the relative load level for load shedding stage
2 (in % of sum of nominal power of running gen-sets or NominMainsImp,
depending on which control quantity is selected) for load reconnection. When
the control quantity drops below this level for more than Ld reconDelay2 time
the next load can be reconnected back.
The appropriate load shedding output is either opened automatically when
the condition above is fulfiled (AutoLd recon = ENABLED) or manually by
activation of the input ManualLdRecon.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.16 Setpoint: Ld reconLevel3
This setpoint is used to adjust the relative load level for load shedding stage
3 (in % of sum of nominal power of running gen-sets or NominMainsImp,
depending on which control quantity is selected) for load reconnection. When
the control quantity drops below this level for more than Ld reconDelay3 time
the next load can be reconnected back.
The appropriate load shedding output is either opened automatically when
the condition above is fulfiled (AutoLd recon = ENABLED) or manually by
activation of the input ManualLdRecon.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.17 Setpoint: LdRecon f lvl1
Ld shed f lvl1 .. 200 [%]