280
11.2.13.20 Setpoint: Ld reconDelay1
Group
Load shedding
Range [units]
0 .. 600 [s]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust time period for load shedding stage1, that the
control quantity must be below the Ld reconLevel1 limit to allow reconnection
of next load group.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.21 Setpoint: Ld reconDelay2
Group
Load shedding
Range [units]
0 .. 600 [s]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust time period for the load shedding stage 2, that
the control quantity must be below the Ld reconLevel2 limit to allow
reconnection of next load group.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.22 Setpoint: Ld reconDelay3
Group
Load shedding
Range [units]
0 .. 600 [s]
Related FW
standard v3.1.0
Force value
possible
YES