InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
279
Force value
possible
YES
Description
This setpoint is used to adjust the relative frequency level for load shedding
stage 1 (in % of nominal system frequency given by setpoints Nominal Freq
and Nom frq offset). When the frequency exceeds this level for more than Ld
reconDelay1 time the next load shedding output is opened.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.18 Setpoint: LdRecon f lvl2
Group
Load shedding
Range [units]
Ld shed f lvl2 .. 200 [%]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust the relative frequency level for load shedding
stage 2 (in % of nominal system frequency given by setpoints Nominal Freq
and Nom frq offset). When the frequency exceeds this level for more than Ld
reconDelay2 time the next load shedding output is opened.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.19 Setpoint: LdRecon f lvl3
Group
Load shedding
Range [units]
Ld shed f lvl3 .. 200 [%]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust the relative frequency level for load shedding
stage 3 (in % of nominal system frequency given by setpoints Nominal Freq
and Nom frq offset). When the frequency exceeds this level for more than Ld
reconDelay3 time the next load shedding output is opened.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.