InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
275
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.8 Setpoint: Ld shed f lvl1
Group
Load shedding
Range [units]
50 .. LdRecon f lvl1 [%]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust the relative frequency level for load shedding
stage 1 (in % of nominal system frequency given by setpoints Nominal Freq
and Nom frq offset). When the frequency goes below this level for more than
Ld shedDelay1 time the next load shedding output is closed.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.9 Setpoint: Ld shed f lvl2
Group
Load shedding
Range [units]
50 .. LdRecon f lvl2 [%]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust the relative frequency level for load shedding
stage 2 (in % of nominal system frequency given by setpoints Nominal Freq
and Nom frq offset). When the frequency goes below this level for more than
Ld shedDelay2 time the next load shedding output is closed.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.10 Setpoint: Ld shed f lvl3
Group
Load shedding
Range [units]
50 .. LdRecon f lvl3 [%]