InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.8 Setpoint: Ld shed f lvl1
This setpoint is used to adjust the relative frequency level for load shedding
stage 1 (in % of nominal system frequency given by setpoints Nominal Freq
and Nom frq offset). When the frequency goes below this level for more than
Ld shedDelay1 time the next load shedding output is closed.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.9 Setpoint: Ld shed f lvl2
This setpoint is used to adjust the relative frequency level for load shedding
stage 2 (in % of nominal system frequency given by setpoints Nominal Freq
and Nom frq offset). When the frequency goes below this level for more than
Ld shedDelay2 time the next load shedding output is closed.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.10 Setpoint: Ld shed f lvl3