InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
This setpoint is used to adjust the relative frequency level for load shedding
stage 3 (in % of nominal system frequency given by setpoints Nominal Freq
and Nom frq offset). When the frequency goes below this level for more than
Ld shedDelay3 time the next load shedding output is closed.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.11 Setpoint: Ld shedDelay1
This setpoint is used to adjust time period for load shedding stage 1, that the
control quantity must be above the Ld shed level limit to close the next load
shedding output.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.12 Setpoint: Ld shedDelay2
This setpoint is used to adjust time period for the load shedding stage 2, that
the control quantity must be above the Ld shedLevel2 limit to close the next
load shedding output.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.