InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
nominal power: 100 * TotRunPact/TotRunPnomAll.
11.2.13.3 Setpoint: Ld shed mode
This setpoint adjusts which type of load shedding is active. When PWR
ONLY is selected the load shedding is based on active power. If FRQ ONLY
is selected the load shedding is based on frequency.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.4 Setpoint: Ld shedStages
This setpoint adjusts the number of load shedding stages that are used in
load shedding.
EXAMPLE:
If 1 load shedding stage is selected the controller will perform one load
shedding stage and rest of the load shedding stages will be omitted.
11.2.13.5 Setpoint: Ld shedLevel1
Ld reconLevel1 .. 200 [%]