Force value
possible
YES
Description
This setpoint is used to adjust the relative load level for load shedding stage
1 (in % of sum of nominal power of running gen-sets or NominMainsImp,
depending on which control quantity is selected) for load shedding. When the
control quantity exceeds this level for more than Ld shedDelay1 time the next
load shedding output is closed.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.6 Setpoint: Ld shedLevel2
Group
Load shedding
Range [units]
Ld reconLevel2 .. 200 [%]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust the relative load level for load shedding stage
2 (in % of sum of nominal power of running gen-sets or NominMainsImp,
depending on which control quantity is selected) for load shedding. When the
control quantity exceeds this level for more than Ld shedDelay2 time the next
load shedding output is closed.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
11.2.13.7 Setpoint: Ld shedLevel3
Group
Load shedding
Range [units]
Ld reconLevel3 .. 200 [%]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust the relative load level for load shedding stage
3 (in % of sum of nominal power of running gen-sets or NominMainsImp,
depending on which control quantity is selected) for load shedding. When the
control quantity exceeds this level for more than Ld shedDelay3 time the next
load shedding output is closed.
NOTE: